STERLING HSB20411 Hot-Water Unit Heater | Montreal, Laval, Longueuil, South Shore & North Shore
The Sterling HSB20411 is a large horizontal hot-water unit heater that blows 2,900 CFM at 1,000 FPM; its hot-water output is confirmed with the manufacturer before the quote.
Model numberHSB20411
514 316-2973 · sales@airgreen.ca
Quick facts
2,900 CFM of warm air for large buildings, with a verified selection
What the Sterling HSB20411 is
The HSB20411 is one of the large horizontal hot-water unit heaters in Sterling’s HS series. Hung from the ceiling, it circulates the water from your loop through a standard header-type coil and blows 2,900 CFM of warmed air, at 1,000 FPM at the outlet, through horizontal louvers that come standard. Its 1/3 HP motor is single speed and runs on 115 V, single phase, 60 Hz.
It is aimed at warehouses and distribution centres, heavy-vehicle garages and large plants heated by an electric boiler, or at replacing a large unit heater on an existing loop.
What we confirm before the quote
We prefer to say it plainly: this model’s hot-water output is not printed identically in the two Sterling documents we consulted. Rather than pick a figure, we confirm it with the manufacturer before giving you a quote. We do the same for the weight, dimensions and pipe connection size, which are not in the verified data.
The hydronic data, on the other hand, is clear. The unit needs 14.9 GPM with a 20°F drop, for a pressure drop of 0.79 ft H2O. That flow matters: the circulator and the piping must be chosen accordingly, especially if the unit heater is added to a loop that already serves other equipment.
Its place in a Quebec building
At AirGreen, we install these unit heaters on electric boilers and air-to-water heat pumps. As with every model in the series, output depends on water temperature: Sterling publishes factors of 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F, 0.429 at 120°F and 0.286 at 100°F, to be applied to the rating measured at 200°F. We do that calculation with the temperature your equipment actually supplies, then compare it with the building’s heat loss.
In a building that can freeze, the loop can contain propylene glycol; Sterling also publishes correction factors for that mix. The coil is rated up to 150 PSI (1,034 kPa) or 320°F (160°C) on hot water and factory tested at 200 psig (1,379 kPa) under water.
Installation by AirGreen
Once the selection is confirmed, our technicians check the structure, hang the unit heater by rods, level, and connect it to the loop with isolation valves and air purging. They make the 115 V electrical connection, install the control and start up the unit while measuring the flow. AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical). We serve Montreal, Laval, Longueuil, the North Shore and the South Shore.
Ask for a free on-site estimate: you receive a written quote based on the rating confirmed by the manufacturer and on your water temperature. Financing is available.
A large volume of warm air for large buildings
The HSB20411 runs 14.9 GPM of hot water through its coil and blows 2,900 CFM from the ceiling. We confirm its exact rating with Sterling before recommending it.
- Warehouse or distribution centre heated by an electric boiler
- Heavy-vehicle garage
- Large plant or workshop
- Replacing a large unit heater on an existing hot-water loop
Specifications
From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.
What to know before installing
- This model’s hot-water output is not printed identically in the two Sterling documents we consulted: we confirm it with the manufacturer before giving you the quote.
- As for the whole series, that output drops below 200°F: Sterling applies 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F and 0.429 at 120°F.
- The circuit must supply 14.9 GPM with a 20°F drop; the circulator is chosen accordingly.
- Single-speed 1/3 HP motor, 115 V. Weight, dimensions and connections are to be confirmed with Sterling; the structure must carry the unit hung level.
Manufacturer documents
Explore the range
Hot-water unit heatersSee allSame brand
STERLINGSee all
Frequently asked questions
What output does the HSB20411 give on hot water?
The two Sterling documents we consulted do not print exactly the same value for this model. We confirm it with the manufacturer before the quote, then apply the factor that matches your water temperature.
Does the “204” in the model number give the output?
No. That code follows another of the manufacturer’s rating bases and does not match the hot-water output.
What water flow should be planned?
14.9 GPM with a 20°F drop, for a pressure drop of 0.79 ft H2O through the coil.
Does it work with an air-to-water heat pump?
Yes, it is a hot-water unit. With cooler water, output drops: Sterling publishes a factor of 0.571 at 140°F and 0.429 at 120°F. We take that into account in the selection.
A large Sterling unit heater, verified and installed by AirGreen
Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.
Specifications from the manufacturer’s documentation, checked on October 19, 2026.