STERLING HSB28011 Hot-Water Unit Heater | Montreal, Laval, Longueuil, South Shore & North Shore

In stock

The Sterling HSB28011 is a 209,100 BTU/h horizontal hot-water unit heater (200°F water) that blows 4,200 CFM, with a 1/2 HP motor on 115 V.

Model numberHSB28011

209,100 BTU/hwith 200°F water (60°F air)
4,200 CFMairflow
1/2 HP115 V motor, single speed
115 V · single phaseHot water or glycolOutput depends on water temperature
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberHSB28011
ManufacturerSterling
Output (200°F water)209,100 BTU/h
Airflow4,200 CFM
Water flow21.0 GPM
Motor1/2 HP, 115 V
MountingHung by rods

4,200 CFM of warm air for very large buildings heated with water

The first size in the series with a 1/2 HP motor

The Sterling HSB28011 marks a new step in the HS series: it is the first size equipped with a 1/2 HP motor. This horizontal hot-water unit heater hangs from the ceiling and blows 4,200 CFM of warmed air, at 980 FPM at the outlet, through horizontal louvers that come standard. With 200°F entering water, 60°F entering air and a 20°F drop, Sterling rates it at 209,100 BTU/h.

It is aimed at very large spaces: light aviation hangar, transfer centre, truck repair shop, large manufacturing plant, whether in Laval, Longueuil, on the North Shore or on the South Shore.

Two points to plan early: electrical and water

On the electrical side, the 1/2 HP motor runs on 115 V, single phase, 60 Hz, single speed. We size the circuit from the nameplate of the unit delivered, and make the connection ourselves.

On the hydronic side, the unit needs 21.0 GPM with a 20°F drop, and its coil’s pressure drop is 1.33 ft H2O. At that flow, the piping, the circulator and the electric boiler’s capacity are chosen at the same time as the unit heater. If several units share the loop, we plan for flow balancing.

Water temperature, glycol and coil

The 209,100 BTU/h rating applies to 200°F water. Sterling publishes the factors to apply below that: 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F, 0.429 at 120°F and 0.286 at 100°F. We do the calculation with the temperature your electric boiler or air-to-water heat pump actually supplies, then compare it with the building’s heat loss.

In a hangar or transfer centre that can freeze, the loop can contain propylene glycol; Sterling publishes correction factors for that mix. The coil is rated up to 150 PSI (1,034 kPa) or 320°F (160°C) on hot water and factory tested at 200 psig (1,379 kPa) under water. According to the manufacturer’s manual, the designs are certified by ETL to CSA C22.2, UL 1995 and UL 60335-2-40.

What our installation covers

We confirm with Sterling the weight, dimensions and connections, which are not in the verified data, and check the structure. Our technicians hang the unit by rods, level, connect it to the loop with isolation valves and air purging, make the electrical connection and the control, then start it up and measure the flow.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical), serving Montreal and the surrounding area.

Ask for a free on-site estimate: you receive a written quote covering the unit, the electrical circuit and the loop, with financing available.

01 · What it is for

For very large spaces heated with water

With 4,200 CFM and a water flow of 21.0 GPM, the HSB28011 is aimed at very large buildings connected to a high-capacity electric boiler.

  • Light aviation hangar
  • Transfer centre
  • Truck repair shop
  • Large manufacturing plant
209,100 BTU/h at 200°FSterling’s rating with 200°F entering water, 60°F entering air and a 20°F drop.
4,200 CFM at 980 FPMThe airflow and outlet velocity published for this size, with horizontal louvers as standard.
1/2 HP motor on 115 VSingle speed, single phase, 60 Hz: the first size in the series with this motor.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerSterling
TypeHorizontal hot-water unit heater, propeller fan
Catalogue designationHS-280
CoilStandard, header type (B)
Hot-water output209,100 BTU/h (200°F entering water, 60°F entering air, 20°F drop)
Airflow4,200 CFM
Outlet air velocity980 FPM
Water flow21.0 GPM (20°F drop)
Water pressure drop1.33 ft H2O
Correction factors (60°F entering air)180°F water: 0.857 · 160°F: 0.715 · 140°F: 0.571 · 120°F: 0.429 · 100°F: 0.286
Motor1/2 HP, single speed
Power supply115 V, single phase, 60 Hz
Coil rating (hot water)Up to 150 PSI (1,034 kPa) or 320°F (160°C)
Factory test200 psig (1,379 kPa), under water
Air outletHorizontal louvers, standard
MountingHorizontal, hung by rods from the connections provided on the unit, level
Heat-transfer fluidHot water or propylene glycol solution (correction factors published by Sterling)
ListingETL
StandardsCSA C22.2, UL 1995, UL 60335-2-40
Model numberHSB28011
03 · Before installing

What to know before installing

  • The electrical circuit is sized from the nameplate of the unit delivered: 115 V, single phase, 60 Hz.
  • The loop must supply 21.0 GPM with a 20°F drop, against a 1.33 ft H2O pressure drop; piping and circulator are chosen accordingly.
  • Below 200°F, output drops: Sterling applies 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F and 0.429 at 120°F.
  • Weight, dimensions and connections are not in the verified data: we confirm them with Sterling and check the structure before installation.
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Hot-water unit heaters
See all
Same brand
STERLING
See all
06 · Questions

Frequently asked questions

Does a 1/2 HP motor on 115 V need a particular circuit?

We size the circuit from the nameplate of the unit delivered. The HSB28011 runs on 115 V, single phase, 60 Hz, and we make the connection during installation.

What water flow and pressure drop?

21.0 GPM with a 20°F drop, for a pressure drop of 1.33 ft H2O through the coil.

What does it give with 180°F water?

Sterling applies a factor of 0.857 at 180°F to the 209,100 BTU/h rating measured at 200°F. We state the result in the quote.

Is the “280” in the model number its output?

No. That code follows another of the manufacturer’s rating bases. On hot water, Sterling publishes 209,100 BTU/h with 200°F water, 60°F air and a 20°F drop.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

An HSB28011 for your very large spaces, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.