STERLING HSB30011 Hot-Water Unit Heater | Montreal, Laval, Longueuil, South Shore & North Shore

In stock

Sterling HSB30011 horizontal hot-water unit heater: 230,000 BTU/h with 200°F water and 5,000 CFM blown at 700 FPM, for large open volumes.

Model numberHSB30011

230,000 BTU/hwith 200°F water (60°F air)
5,000 CFMairflow
700 FPMoutlet air velocity
115 V · 1/2 HPHot water or glycolOutput depends on water temperature
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberHSB30011
ManufacturerSterling
Output (200°F water)230,000 BTU/h
Airflow5,000 CFM
Water flow23.0 GPM
Pressure drop2.1 ft H2O
Power supply115 V, 1 ph, 60 Hz

5,000 CFM to heat large open volumes

A large airflow, blown at 700 FPM

The Sterling HSB30011 is one of the largest horizontal hot-water unit heaters in the HS series. Hung below the ceiling, it runs the water from your loop through a standard header-type coil and moves 5,000 CFM of warmed air, at 700 FPM at the outlet, through horizontal louvers that come standard. Sterling rates it at 230,000 BTU/h with 200°F entering water, 60°F entering air and a 20°F drop.

Its 1/2 HP motor is single speed and runs on 115 V, single phase, 60 Hz; we size the circuit from the nameplate. We propose it for the receiving and shipping areas of large warehouses, assembly plants and the service centres of transit companies.

A selection that starts with the water

A unit of this size is not chosen on its rating alone. The 230,000 BTU/h value is measured at 200°F; with cooler water, Sterling publishes the factors to apply: 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F, 0.429 at 120°F and 0.286 at 100°F. We do the calculation with the temperature your electric boiler or air-to-water heat pump actually supplies, then compare it with the heat loss.

The loop, for its part, must supply 23.0 GPM with a 20°F drop, against a 2.1 ft H2O pressure drop through the coil. The circulator, the piping and the boiler’s capacity are therefore chosen at the same time as the unit heater. If part of the loop can freeze, it can contain propylene glycol, for which Sterling publishes correction factors.

A measured start-up

We first confirm with Sterling the weight, dimensions and connections, which are not in the verified data, then check the structure. Our technicians hang the unit by rods, level, connect it with isolation valves and air purging, and make the electrical connection and the control.

Start-up does not stop when the fan turns on. We measure the water flow and the temperature difference between inlet and outlet, and compare them with the conditions Sterling publishes. That is what confirms the unit receives the water it needs.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical). We serve Montreal, Laval, Longueuil, the North Shore and the South Shore.

Let’s plan your large space

Ask for a free on-site estimate: you receive a written quote covering the unit, the loop and the start-up, with financing available.

01 · What it is for

A large volume of air for open spaces

The HSB30011 moves 5,000 CFM at 700 FPM at the outlet. We propose it for large open spaces connected to a high-capacity electric boiler, after a calculation made at your water temperature.

  • Receiving and shipping area of a large warehouse
  • Assembly plant
  • Service centre of a transit company
  • Large industrial building heated with water
230,000 BTU/h at 200°FSterling’s rating with 200°F entering water, 60°F entering air and a 20°F drop.
5,000 CFMAirflow published for this size, blown at 700 FPM through horizontal louvers that come standard.
Coil tested at 200 psigFactory tested at 200 psig (1,379 kPa) under water; rated up to 150 PSI (1,034 kPa) or 320°F (160°C) on hot water.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerSterling
TypeHorizontal hot-water unit heater, propeller fan
Catalogue designationHS-300
CoilStandard, header type (B)
Hot-water output230,000 BTU/h (200°F entering water, 60°F entering air, 20°F drop)
Airflow5,000 CFM
Outlet air velocity700 FPM
Water flow23.0 GPM (20°F drop)
Water pressure drop2.1 ft H2O
Correction factors (60°F entering air)180°F water: 0.857 · 160°F: 0.715 · 140°F: 0.571 · 120°F: 0.429 · 100°F: 0.286
Motor1/2 HP, single speed
Power supply115 V, single phase, 60 Hz
Coil rating (hot water)Up to 150 PSI (1,034 kPa) or 320°F (160°C)
Factory test200 psig (1,379 kPa), under water
Air outletHorizontal louvers, standard
MountingHorizontal, hung by rods from the connections provided on the unit, level
Heat-transfer fluidHot water or propylene glycol solution (correction factors published by Sterling)
ListingETL
StandardsCSA C22.2, UL 1995, UL 60335-2-40
Model numberHSB30011
03 · Before installing

What to know before installing

  • The loop must supply 23.0 GPM with a 20°F drop, against a 2.1 ft H2O pressure drop through the coil.
  • Below 200°F, output drops: Sterling applies 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F and 0.429 at 120°F.
  • Single-speed 1/2 HP motor, 115 V, single phase, 60 Hz; the circuit is sized from the nameplate.
  • Weight, dimensions and connections are not in the verified data: we confirm them with Sterling and check the structure before installation.
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Hot-water unit heaters
See all
Same brand
STERLING
See all
06 · Questions

Frequently asked questions

How do you check that the unit gets the right flow?

At start-up, we measure the flow and the temperature difference between water inlet and outlet, then compare them with the conditions Sterling publishes: 23.0 GPM with a 20°F drop.

Why a 700 FPM outlet velocity?

It is the velocity Sterling publishes for this size, with 5,000 CFM of airflow. Mounting height and air throw are not in the verified data; we establish them with the manufacturer’s manual.

What does it give with 140°F water?

Sterling applies a factor of 0.571 at 140°F to the 230,000 BTU/h rating measured at 200°F. The result appears in the quote.

Is a glycol loop needed?

Only if part of the loop could freeze. Sterling then publishes correction factors for propylene glycol, which we apply to the calculation.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

An HSB30011 commissioned by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.