STERLING HSB24011 Hot-Water Unit Heater | Montreal, Laval, Longueuil, South Shore & North Shore

In stock

Sterling HSB24011 horizontal hot-water unit heater: 174,000 BTU/h with 200°F water and 3,500 CFM, for large buildings whose loop is designed to match.

Model numberHSB24011

174,000 BTU/hwith 200°F water (60°F air)
3,500 CFMairflow
17.4 GPMwater flow, 20°F drop
115 V · 1/3 HPHot water or glycolOutput depends on water temperature
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberHSB24011
ManufacturerSterling
Output (200°F water)174,000 BTU/h
Airflow3,500 CFM
Water flow17.4 GPM
Pressure drop1.06 ft H2O
Power supply115 V, 1 ph, 60 Hz

A large unit heater whose loop is designed along with the unit

The HSB24011 in published figures

The Sterling HSB24011 is a horizontal hot-water unit heater from the HS series. Hung from the ceiling, it blows 3,500 CFM of warmed air, at 900 FPM at the outlet, through horizontal louvers that come standard. Sterling rates it at 174,000 BTU/h with 200°F entering water, 60°F entering air and a 20°F drop. Its single-speed 1/3 HP motor connects on 115 V, single phase, 60 Hz.

This size targets distribution centres, heavy machinery maintenance shops and storage hangars, in buildings equipped with a good-sized electric boiler.

Designing the loop: flow, pressure drop and balancing

At this size, the unit is no longer chosen on its own. It needs 17.4 GPM with a 20°F drop, and its coil’s pressure drop reaches 1.06 ft H2O. The circulator must supply that flow on top of the other circuits; depending on the case, we keep the existing circulator or propose a dedicated one.

If the building receives several unit heaters, the loop must be designed for all the flows, with balancing valves so that each unit gets its share. We draw that layout before the quote, and the electric boiler must have capacity to spare for the whole system, at the chosen temperature.

Water temperature and loop fluid

The 174,000 BTU/h rating applies to 200°F water. Below that, Sterling publishes the factors to apply: 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F, 0.429 at 120°F and 0.286 at 100°F. With an air-to-water heat pump, a larger size or an extra unit may be needed; we present the options, with the calculation to back them.

In a hangar that can freeze, the loop can contain propylene glycol, for which Sterling publishes correction factors. The coil is rated up to 150 PSI (1,034 kPa) or 320°F (160°C) on hot water and factory tested at 200 psig (1,379 kPa) under water.

What our installation covers

We confirm the weight, dimensions and connections with Sterling, then check the structure that will carry the unit. Our technicians hang it by rods, level, connect it to the loop with isolation valves, balancing valves as needed and air purging, make the 115 V electrical connection and the control, then start it up and measure the flows.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical). We serve Montreal, Laval, Longueuil, the South Shore and the North Shore.

Ask for a free on-site estimate: your written quote covers the unit, the loop and the circulator, and financing is available.

01 · What it is for

When the loop matters as much as the unit

At 17.4 GPM and a 1.06 ft H2O pressure drop, the HSB24011 weighs on the loop design. We size the circulator, the piping and the balancing at the same time as the unit.

  • Regional distribution centre
  • Heavy machinery maintenance shop
  • Storage hangar for a construction company
  • Industrial building with a large electric boiler
174,000 BTU/h at 200°FSterling’s rating with 200°F entering water, 60°F entering air and a 20°F drop.
3,500 CFMAirflow published for this size, blown at 900 FPM through horizontal louvers that come standard.
1/3 HP motor on 115 VSingle speed, single phase, 60 Hz, according to the manufacturer.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerSterling
TypeHorizontal hot-water unit heater, propeller fan
Catalogue designationHS-240
CoilStandard, header type (B)
Hot-water output174,000 BTU/h (200°F entering water, 60°F entering air, 20°F drop)
Airflow3,500 CFM
Outlet air velocity900 FPM
Water flow17.4 GPM (20°F drop)
Water pressure drop1.06 ft H2O
Correction factors (60°F entering air)180°F water: 0.857 · 160°F: 0.715 · 140°F: 0.571 · 120°F: 0.429 · 100°F: 0.286
Motor1/3 HP, single speed
Power supply115 V, single phase, 60 Hz
Coil rating (hot water)Up to 150 PSI (1,034 kPa) or 320°F (160°C)
Factory test200 psig (1,379 kPa), under water
Air outletHorizontal louvers, standard
MountingHorizontal, hung by rods from the connections provided on the unit, level
Heat-transfer fluidHot water or propylene glycol solution (correction factors published by Sterling)
ListingETL
StandardsCSA C22.2, UL 1995, UL 60335-2-40
Model numberHSB24011
03 · Before installing

What to know before installing

  • The circulator must supply 17.4 GPM through the coil (1.06 ft H2O pressure drop), on top of the loop’s other circuits.
  • Below 200°F, output drops: Sterling applies 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F and 0.429 at 120°F.
  • The electric boiler must have capacity to spare at the chosen temperature.
  • Weight, dimensions and connections are not in the verified data: we confirm them with Sterling and check the structure before installation.
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Hot-water unit heaters
See all
Same brand
STERLING
See all
06 · Questions

Frequently asked questions

Does it need a dedicated circulator?

Not necessarily. The circulator must supply 17.4 GPM through the coil, whose pressure drop is 1.06 ft H2O, on top of the other circuits. We do that calculation and propose a dedicated circulator if one is needed.

Can several HSB24011 units go on the same loop?

Yes, with a loop designed for all the flows and balancing valves, so that each unit receives its flow. We draw that layout before the quote.

What does it give with 160°F water?

Sterling applies a factor of 0.715 at 160°F to the 174,000 BTU/h rating measured at 200°F. The result appears in our quote.

Does it suit an air-to-water heat pump?

Yes, but with cooler water the output drops: factor of 0.571 at 140°F and 0.429 at 120°F. A larger size or an extra unit may then be needed; we present the options to you.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

An HSB24011 and its loop, designed and installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.